A student-run house at Cal Poly Humboldt (then HSU) chose not to use batteries for its solar panels. The Campus Center for Appropriate Technology (CCAT), started in 1978, is a live-in demonstration house and educational center, and its rooftop photovoltaic (PV) system was meant to be a working example for visitors. The project was sponsored by the Humboldt Energy Independence Fund, an entirely student-funded organization.
A short history
CCAT put in its first PV system in May 1991. It ran off the grid for ten years, together with a wind turbine and a backup biodiesel generator. The old stand-alone system had 22 Solec International panels, donated in the 1980s from the Flat Plate Array Project at the Jet Propulsion Laboratory, which made about 700 watts at peak on a sunny summer day. The wind turbine, 43 feet tall, produced little because the trees around the site had grown.
The current system is grid-tied. It was installed in 2001, ran until 2005, was taken off when the house was moved several hundred feet to make room for a new building, and was reconnected in 2008.
Why no batteries
The design centred on a donation of eight large panels (ASE-300-DGF/17, 4 by 6 feet, 300 watts each) from ASE Americas. Four wired in series make a building block of roughly 1 kW at 48 V, after deducting 12 percent from the rated output to reflect normal conditions.
The team's reasoning on inverters is the most instructive part:
- The Trace SW4024 they already owned needed a small battery bank and, when the panels were not charging, kept float-charging the batteries from the grid. With the minimum 100 amp-hour bank they expected to lose at least a few hundred watt-hours a day, perhaps 1 to 2 kWh, an efficiency loss of 5 to 25 percent. Adding a voltage-controlled relay would have complicated the system and made it less typical.
- The Trace Sun Tie ST2500 needed no batteries, but Trace had had serious problems with its maximum power point tracking, so the team would not risk it.
- The Advanced Energy GC-1000 was the one remaining inverter certified by the California Energy Commission and configured for 48 V input. It is rated at 1 kW with peak efficiency of 93 percent. Advanced Energy donated two refurbished units and a data monitor, and the team still chose certified equipment so that the utility would approve it without question.
Their view on batteries: unless you really need backup power, a grid-connected system should not have them. Batteries add cost, need regular maintenance and periodic replacement, and add inefficiency, and in most places the grid is rarely down for long.
Testing and installing
Before installation the team measured current-voltage curves for each of the eight panels, in June 2001. They were donated "leftovers" with cosmetic defects, yet their output was within 1 percent of the manufacturer's measurements and within 2 percent of their nameplate rating. ASE rates its panels to plus or minus 4 percent, where most makers use plus or minus 10 percent, which the CCAT team found laudable.
The house's old wiring needed bringing up to code first, which a local electrical contractor did. A solar contractor ran the DC wire and helped install the panels and inverters, with students from a PV design and installation class. The panels sit about 3 inches above the roof on RoofJack mounts, which let air circulate to cool them. The roof faces due south at a slope of 26.5 degrees; at Arcata's latitude of 41 degrees north that is within 15 degrees of the latitude, the recommended range.
What it produced
The system first generated on October 17, 2001. By April 23, 2002 it had made 901 kWh, of which 358 kWh were used on site and 543 kWh fed back to PG&E. The house averaged 1.9 kWh a day of use, and the panels averaged 4.8 kWh a day. The team expected about 1.8 kW of peak AC power and 7.2 kWh a day, far above what the house needed. In one month of data, the maximum AC output was 1,745 W, and about 99 percent of the time the input voltage stayed within the inverters' tracking range of 55 to 70 volts. In the first months the only problem was a blown fuse on a DC input, which the team suspected was caused by sunlight reflecting off clouds.
The net metering lesson
Because PG&E pays nothing for surplus electricity, the best a net-metered California household can do is bring its annual bill to the minimum monthly charge, then US$5. The CCAT system was deliberately oversized, which would not be cost-effective for a typical homeowner, but most of its equipment was donated. The team also looked at the time-of-use rate, which would have needed a US$277 meter. It values summer peak hours (noon to 6 PM on weekdays, May through October) at about 32 cents per kWh, against about 12 cents in winter peak periods and about 9 cents off-peak. Because CCAT made far more than it used, the time-of-use rate would not have helped it.
Repairs in 2018 and 2019
The panels' inverter, an Aurora 3600-US-OUT, had kept blinking "Waiting on Sun," and in spring 2018 co-director Anh Bui found it was not working properly. A new Fronius Primo 3.8 kW inverter was bought (the system cost US$1,271 in December 2018) and installed in 2019 by local solar experts who volunteered their time on a rainy day.
In spring 2019 the new inverter showed a "LOW PV VOLTAGE" state and a notice that no energy had been fed to the grid in 24 hours. After a call to Fronius support did not help, the installer and CCAT co-director Jacob Gellatly found a blown fuse. They also found the panels wired as two series strings of four rather than all eight in one series, as recorded in the 2014 design, and rewired them to eight in series. The page adds that the low-voltage codes also appear routinely in early morning and evening, when sunlight is weak, and do not indicate a fault.

The inverter and its open disconnect. Photo: DomT on Appropedia, CC BY-SA 3.0.

The disconnect wiring. Photo: DomT on Appropedia, CC BY-SA 3.0.