St. Michael's after the 1886 earthquake: the portico leaned toward Meeting Street and was rebuilt, and large cracks in the first bay were repaired.
A tall timber steeple stands or falls on how it is anchored to the building below. This article, the fifth in a series on the form, function and joinery of historic American timber-framed steeples (developed from original research under a grant from the National Park Service and the National Center for Preservation Technology and Training), explains how engineer David C. Fischetti analyzed and restored one of the best known: the 186-foot steeple of St. Michael's Episcopal Church in Charleston, South Carolina.
How steeples are analyzed
A steeple may stand on its own foundation or be built into the end wall or side wall of a church. Many on roofs have two posts on the church's end wall and two on the first interior roof truss, often passing through a balcony. Steeples made of stacked square, hexagonal or octagonal stages, with a spire on top, may call for a three-dimensional analysis; others suit a flat, two-dimensional one. In either case the wind and earthquake forces should be applied in four directions, across the ridge of the main roof and along it.
Many roof-mounted steeples lean back toward the nave when an end wall and a less stiff roof truss share the load, and a steeple will eventually lean if the end wall is unyielding masonry: a bit of shrinkage across the grain in several large timber plates on the nave side can add up to a dramatic tilt. For analysis the frame is reduced to posts, beams and braces. A first run shows which braces are in tension or compression, and those that cannot carry the tension are removed from the model before it is re-run. Computers let an engineer model hinged or continuous joints, half-lapped or intersecting members and springs that allow a given movement, so the stiffness of a timber frame can be found more accurately. Sheathing and panels that are firmly fastened add stiffness and should be counted too.
The church
Samuel Cardy built St. Michael's between 1752 and 1761, following English pattern-book designs popular in the colonies and resembling James Gibbs's St. Martin-in-the-Fields in London. It survived wars, hurricanes, tornadoes, fires and the 1886 earthquake, which settled the steeple 8 inches and leaned the spire 18 inches away from the nave. During the Revolutionary War it was a center of American resistance and British naval gunners targeted its tower. Hurricane Hugo, a Category 4 storm that struck in September 1989, bent the wrought-iron bar that carries the weather vane and led to a $6 million insurance settlement.

Cutaway elevation of the steeple, looking south (Historic American Buildings Survey, 1963, drawn by Mark W. Steele).
The steeple has five stages above the roof. The first is a square brick tower, the second and third (the bell and clock stages) rise as a masonry box that changes from square to octagon, and the open lantern and the spire above are timber framed. The brick walls are between 4 feet 9½ inches and 5 feet 3 inches thick. The church's own roof trusses are independent of the steeple.
Finding the problem
After Hugo, materials conservator George Fore produced a condition study that located deteriorated wood. A surveyor's attempt to measure the lean was inconclusive, so Fischetti inspected in person on a day with wind gusts of 5 to 10 mph, climbing with Craig Bennett, P.E., of Cummings and McCrady, architects. In the lantern they could feel it sway and hear the timbers rub. Behind each of its eight arched openings was a portal frame of two knee braces with a wedge between them, a perimeter beam and two posts.
The worrying feature was horizontal steel beams added in 1938, apparently for extra vertical support. To fit them, the eight original 8x8 core posts descending from the spire had been cut two-thirds through. The original designer had built in a good way to resist wind: the bundle of eight timbers, telescoping up from the masonry like a flagpole in the ground, acts as a vertical cantilever. The steel had interrupted its continuity. The September 1990 preliminary report recommended removing the deteriorated steel, filling the masonry pockets and repairing the damaged members with epoxy consolidation, epoxy-aided splicing and replacement in kind, without altering the structural system or sacrificing historic fabric.
The model
A final report in May 1992 gave a simple analysis. It used a Use Factor of 1.00 from the 1988 Standard Building Code, because failure of the spire seemed unlikely to affect 300 or more people in the sanctuary, which is used mainly one day a week. The spire and lantern frame was modeled with the stiffness of two portal frames, ignoring knee braces in tension, and with a spring support to imitate lantern posts not tied down. Under a 100-mph wind, the computed horizontal movement at the top of the frame was:
| Condition | Deflection |
|---|---|
| As built | 2.13 inches |
| Deteriorated | 5.43 inches |
That fit what was seen: much larger movements would be rupturing the sheathing and carved millwork. Fore's study had found fractured paint lines at some joints where the lantern's horizontal planks had slipped, so the stage had racked. Stresses in the members were low, as expected in timber frames where connections govern, and the highest were in the interior core posts at the top of the lantern stage, where bending acts on a small section. The original scribed marks used to match timbers turned out to correspond to compass points.
The repair
The analysis supported replacing severely deteriorated members entirely and repairing the deteriorated ends of others. The timber framer, Tommy Graham, proposed repairing with "Dutchmen" (inserted patches) and a gap-filling epoxy to keep as much historic wood as possible, and he pointed out how hard it would be to get large dense cypress timbers dried to match the old frame. To test the epoxy, six small half-lapped specimen joints made in field conditions were tensile-tested at North Carolina State University. They broke at a fairly uniform average of 857 psi, and the design applied a factor of safety of four to that average to size moment splices between original wood and rebuilt ends of several of the "spider beams," the radial horizontal timbers below the lantern floor.
New tenoned post ends were made of dense cypress at 14 to 16 percent moisture content, close to the 11 to 14 percent of the old frame. A totally decayed strut was replaced by five cypress boards laminated on edge. Badly deteriorated spider beams were replaced with pressure-treated Southern yellow pine, and iron straps that had disintegrated were replaced with stainless steel. The lantern's lead-covered floor, once opened, proved to be caulked with oakum and tar, and it was later covered with sheet copper.
The restoration took an architect, an engineer, a conservator, a timber framer, a general contractor and a representative of the church, who joined day-to-day decisions.