Автора пока нетВзять себе
- Лицензия
- CC0 1.0 (общественное достояние)По материалам www.epa.gov
- Языки
- English
Leaks are where a commercial building should look first for water savings: on average, they can account for more than 6 percent of a facility's total water use. This guidance from EPA's WaterSense program is for facility managers who are just starting on water efficiency. The case for acting is cost. The costs of water and wastewater service have risen well above the consumer price index over the past few decades, and facility managers can expect them to keep climbing as communities pay to replace aging supply systems.
The business case
Carrying out and communicating water efficiency efforts can mark a company as a sustainability leader and bring recognition in the green marketplace. WaterSense lists these benefits for commercial and institutional facilities: cost savings, competitive advantage, lower risk from water scarcity, a chance to show leadership, and access to opportunities in the green building market. Cutting water use also cuts the energy needed to heat, store and deliver it. WaterSense points to Providence Hospital in Olympia, Washington, as an example.
Plan first
Effective water management starts with planning. Facilities should consider a water management team to evaluate use, develop implementation plans, measure progress and set new savings goals. A plan generally targets four areas:
- reducing water losses, such as leaks;
- raising the efficiency of fixtures, equipment, systems and processes;
- educating employees and occupants to encourage water-saving habits;
- reusing onsite alternative water that would otherwise be discarded or sent to the sewer, such as treated graywater or rainwater for landscaping.
The framework is the one in the ENERGY STAR Guidelines for Energy Management: make a commitment, assess facility water use, set and communicate goals, create an action plan, implement it, evaluate progress, and recognize achievement. Periodic reviews by the team show and promote the program's success, which can build support for later projects.
Measure with meters and submeters
"You can't manage what you don't measure." Meters and submeters let managers identify areas for targeted reductions, find and fix leaks and malfunctioning equipment, spot more savings and track the savings from projects. They can feed a central building management system that stores hourly, daily, monthly and annual use and raises alerts when it detects leaks or operating anomalies. Submeters and temporary flow meters do not need separate utility accounts; they can serve just to locate problems. Choosing the right meter and keeping it working is critical to accurate measurement.
Many utilities are moving to Advanced Metering Infrastructure (AMI), which collects more frequent data, such as hourly, that helps managers understand use and find leaks.
Hunt for leaks
Leaks and continuously running water are not always visible but can quickly become a major cost in water and energy bills. To find them:
- track water and energy use, and read meters and submeters to catch spikes before a high bill arrives;
- set up alerts for leaks and failures in water-using equipment such as cooling towers and boiler systems;
- add leak detection to daily rounds and have staff, visitors and tenants report leaks;
- use WaterSense checklists, and write down the leaks found so savings can be estimated and used to keep people looking.
WaterSense also suggests borrowing from its annual Fix a Leak Week, held each March: challenge employees and tenants to find leaks, ask the local utility to help, post signs in restrooms and kitchens with maintenance contacts, include leak detection in staff training and in service and vendor contracts, and pass the message to outsourced cleaning, housekeeping, maintenance and landscaping staff and to tenants.
What leaks can cost
| Malfunction | Flow rate | Water lost | Estimated cost |
|---|---|---|---|
| Small toilet leak, e.g. a worn flapper | 0.02 gallons per minute | 860 gallons a month | Up to $10 a month |
| Medium toilet leak, e.g. a misaligned flapper | 0.2 gallons per minute | 8,600 gallons a month | Up to $95 a month |
| Large toilet leak, e.g. a stuck fill valve | 3.0 gallons per minute | 4,300 gallons a day | Up to $1,400 a month |
| Drip irrigation malfunction | 1.0 gallon per minute | 43,200 gallons a month | $5,700 a year |
| Unattended water hose at night | 10.0 gallons per minute | 5,400 gallons a day | $60 a day |
| Broken distribution line | 15.0 gallons per minute | 8,100 gallons in one night, 21,600 in one day, 151,200 in one week, 648,000 in one month | Up to $7,200 a month |
| Steam sterilizer tempering water line stuck on | 2.0 gallons per minute | 86,400 gallons a month | $11,500 a year |
| Stuck float valve in a cooling tower | 5.0 gallons per minute | 216,000 gallons a month | $29,000 a year |
Sources
- U.S. Environmental Protection Agency, WaterSense, Getting Started (commercial buildings); rewritten in hubnx's own words.